CCB HOME>PRODUCTS>CD SERIES>CCB12CD-100


 

FEATURES

* Maintenance Free

* Leak Proof / Spill Proof

* Gas Recombination

* Absorbed Electrolyte

* Float / Cycle Use

* Low Self Discharge Rate

* Safety Valve

* Lead Calcium Alloy

* Useable In Any Position

* Rugged Design

* Available Flame Retardent Material (Optional)


VRLA 12V100Ah - Specifications

Nominal Voltage

Rated Capacity @20hr rate

Maximum Charge Rate

Maximum Discharge Amps 5 sec.

Internal Resistance

12V

100Ah

50Amps

900Amps

3.9Mili Ohms

Capacity
@ 77
F (25C)

100.00Ah @ 20 hour rate (5.00A) to 1.75 volts per cell

90.00Ah @ 10 hour rate (9.00A) to 1.75 volts per cell

78.00Ah @ 5 hour rate (15.60A) to 1.75 volts per cell

71.00Ah @ 3 hour rate (23.67A) to 1.75 volts per cell

55.00Ah @ 1 hour rate (55.00A) to 1.75 volts per cell

Dimensions

Length

330mm (13.00inches)

Width

175mm (6.89inches)

Height

215mm (8.47inches)

Total Height

220mm (8.67inches)

Weight

29kg (63.80lbs)

Operating Temperature Range

Discharge

-4F (-20C) to +140F (60C)

Charge

14F (20C) to +122F (50C). (with temperature compensation)

Recommonded Operating Temperature Range

+68F (20C) to +77F (25C).

Charging (Constant Voltage)

Cycle use

Initial Current 20Amps (recommended).

Voltage 14.5-14.9Volts @77F (25C)

Float use

Voltage 13.6-13.8Volts @77F (25C)

Self Discharge
@ 77
F (25C)

Capacity after 3 month storage

90%

Capacity after 6 month storage

80%

Capacity after 12 month storage

60%

CCB Battery may be stored for up to 12 months at 77F (25C) and then a freshing charge is required. For higher temperatures the time interval will be shorter.

Capacity affected by Temperature (20 hour rate)

104F (40C)

102%

77F (25C)

100%

32F (0C)

85%

58F (-15C)

65%

Notice: The above data are average values, and could be obtained within 3 charge / discharge cylcles.These are not minimum values.

CCB12CD-100 Plan

Discharge Curves

Discharging Current&Duration Time

Click here for larger size image!

CCB BATTERY * * * THE ENGINE OF PROGRESS... ...