VRLA
12V2.2Ah - Specifications |
Nominal Voltage |
Rated Capacity @20hr rate |
Maximum Charge Rate |
Maximum Discharge Amps 5 sec. |
Internal Resistance |
|
12V |
2.2Ah |
1.1Amps |
60Amps |
90Mili Ohms |
|
Capacity
@ 77━F (25━C) |
2.20Ah @ 20 hour rate
(110mA) to 1.75 volts per cell |
2.00Ah @ 10 hour rate (200mA) to 1.75 volts
per cell |
1.80Ah @ 5 hour rate (360mA) to 1.75 volts
per cell |
1.65Ah @ 3 hour rate (550mA) to 1.75 volts
per cell |
1.45Ah @ 1 hour rate (1.45A) to 1.75 volts
per cell |
Dimensions |
Length |
182mm (7.17inches) |
|
Width |
24mm (0.95inches) |
|
Height |
60mm (2.37inches) |
|
Total Height |
60mm (2.37inches) |
|
Weight |
0.99kg (2.18lbs) |
Operating Temperature
Range |
Discharge |
-4━F (-20━C) to +140━F (60━C) |
|
Charge |
14━F (-10━C) to +122━F (50━C). (with temperature compensation) |
|
Recommonded Operating
Temperature Range |
+68━F (20━C) to +77━F (25━C). |
Charging (Constant
Voltage) |
Cycle use |
Initial Current 0.44Amps (recommended). |
|
Voltage 14.5-14.9Volts @77━F (25━C) |
|
Float use |
Voltage 13.6-13.8Volts @77━F (25━C) |
|
Self Discharge
@ 77━F (25━C) |
Capacity after 3 month storage |
90% |
Capacity after 6 month storage |
80% |
Capacity after 12 month storage |
60% |
CCB Battery may be stored for up to 12 months
at 77━F (25━C) and then a freshing charge is required.
For higher temperatures the time interval will be shorter. |
Capacity
affected by Temperature (20 hour rate) |
104━F (40━C) |
102% |
77━F (25━C) |
100% |
32━F (0━C) |
85% |
58━F (-15━C) |
65% |
Notice: The above data are average values,
and could be obtained within 3 charge / discharge cylcles.These
are not minimum values. |