CCB HOME>PRODUCTS>CD SERIES>CCB12CD-33


 

FEATURES

* Maintenance Free

* Leak Proof / Spill Proof

* Gas Recombination

* Absorbed Electrolyte

* Float / Cycle Use

* Low Self Discharge Rate

* Safety Valve

* Lead Calcium Alloy

* Useable In Any Oosition

* Rugged Design

* Available Flame Retardent Material (Optional)


VRLA 12V33Ah - Specifications

Nominal Voltage

Rated Capacity @20hr rate

Maximum Charge Rate

Maximum Discharge Amps 5 sec.

Internal Resistance

12V

33Ah

16.5Amps

330Amps

9Mili Ohms

Capacity
@ 77
F (25C)

33.00Ah @ 20 hour rate (1.65A) to 1.75 volts per cell

30.20Ah @ 10 hour rate (3.02A) to 1.75 volts per cell

28.00Ah @ 5 hour rate (5.60A) to 1.75 volts per cell

25.00Ah @ 3 hour rate (8.33A) to 1.75 volts per cell

19.80Ah @ 1 hour rate (19.80A) to 1.75 volts per cell

Dimensions

Length

195mm (7.68inches)

Width

130mm (5.12inches)

Height

164mm (6.44inches)

Total Height

180mm (7.07inches)

Weight

11kg (24.20lbs)

Operating Temperature Range

Discharge

-4F (-20C) to +140F (60C)

Charge

14F (-10C) to +122F (50C). (with temperature compensation)

Recommonded Operating Temperature Range

+68F (20C) to +77F (25C).

Charging (Constant Voltage)

Cycle use

Initial Current 6.6Amps (recommended).

Voltage 14.5-14.9Volts @77F (25C)

Float use

Voltage 13.6-13.8Volts @77F (25C)

Self Discharge
@ 77
F (25C)

Capacity after 3 month storage

90%

Capacity after 6 month storage

80%

Capacity after 12 month storage

60%

CCB Battery may be stored for up to 12 months at 77F (25C) and then a freshing charge is required. For higher temperatures the time interval will be shorter.

Capacity affected by Temperature (20 hour rate)

104F (40C)

102%

77F (25C)

100%

32F (0C)

85%

58F (-15C)

65%

Notice: The above data are average values, and could be obtained within 3 charge / discharge cylcles.These are not minimum values.

CCB12CD-33 Plan

Discharge Curves

Discharging Current&Duration Time

Click here for larger size image!

CCB BATTERY * * * THE ENGINE OF PROGRESS... ...