VRLA
2V1500Ah - Specifications |
Nominal Voltage |
Nominal Ampere Hour Capacity
@10hr rate to 1.80VPC at 25━C |
Internal Resistance |
|
2V |
1500Ah |
0.08Mili Ohms |
|
Capacity
@ 77━F (25━C) |
1500Ah @ 10 hour rate
(150.00A) to 1.80 volts per cell |
1380Ah @ 5 hour rate (276.00A) to 1.80 volts
per cell |
1260Ah @ 3hour rate (420.00A) to 1.80 volts
per cell |
975Ah @ 1 hour rate (975.00A) to 1.80 volts
per cell |
Dimensions |
Length |
400mm (15.75inches) |
|
Width |
350mm (13.78inches) |
|
Height |
345mm (13.59inches) |
|
Total Height |
382mm (15.04inches) |
|
Weight |
100kg (220lbs) |
Operating
Temperature Range |
Discharge |
-4━F (40━C) to +140━F (60━C) |
|
Charge |
14━F (20━C) to +122━F (50━C).
(with temperature compensation) |
|
Recommonded Operating Temperature Range |
+68━F (20━C) to +77━F (25━C). |
Charging
(Constant Voltage) |
Float Voltage |
2.25VPC +/- 1% @77━F (25━C) |
|
Maximum Charge Voltage |
2.40VPC @77━F (25━C) |
|
Self Discharge
@ 77━F (25━C) |
Capacity after 3 month storage |
90% |
|
Capacity after 6 month storage |
80% |
|
Capacity after 12 month storage |
60% |
|
CCB Battery may be stored for up to 12 months
at 77━F (25━C) and then a freshing charge is required.
For higher temperatures the time interval will be shorter. |
Capacity
affected
by Temperature
(20 hour rate) |
104━F (40━C) |
102% |
|
77━F (25━C) |
100% |
|
32━F (0━C) |
85% |
|
58━F (-15━C) |
65% |
|
Notice: The above data are average values,
and could be obtained within 3 charge/discharge cylcles.
These are not minimum values. |